WARNING!

WARNING!

Shock Hazard: Unburdened CT's should never be handled with primary current applied!

CT Calculation Helper

Enter the information below to calculate the burden resistor required for Current Transformers that do NOT contain a built-in burden resistor.

Do I need a burden resistor?

Some CT's contain a built-in burden resistor.  If the CT is rated in Volts per Amp (for example 0.333V at 100A) then it already contains a built-in burden resistor.

If a CT is rated as a turns ratio, then it likely does NOT contain a burden resistor.  The calculator below can be used to determine the desired burden resistor value.

CT Operation

A CT encloses a primary current (Ip) and produces a secondary current (Is) through the seconday winding of N turns (the turns ratio). 

The voltage produced across the burden resistor (R) is given by the accompanying equation.

The following calculator can be used to determine a suitable burden resistor for use with the Z3 NetMeter:

Burden Resistor Calculator
(Amps RMS)
(Volts RMS)
(Number of turns of the secondary winding)
(Ohms)
(Watts)
 
CT Primary Current Calculator (burden resistor value known)
(Amps RMS)
(Volts RMS)
(Number of turns of the secondary winding)
(Ohms)
(Watts)